• +44 20 8895 6455
  • info@webbinfra.com

Data Center Fire Systems


Rack Mountable Fire Systems

Webb’s rack mountable fire extinguishers are specialized fire suppression systems designed to safeguard critical IT components within server cabinets. They are equipped with FM200/Novec-1230 gas, releasing valves, activation sensors and controllers, making them the ideal choice for protecting self-contained data center systems from fire damage.


Technical specifications

  • Available in three models: T.MDC.FM.FE.1.3, T.MDC.FM.FE.4.6, T.MDC.FM.FE.8.6
  • Main power: AC220V 50/60Hz
  • Standby power: 1.5W
  • Storage Pressure: 1.6MPa (1.3MPa to 2.5MPa)
  • Battery time: 8 hours
  • Temperature threshold: 62°C ± 8°C
  • Extinguishing delay: 30s
  • Gas type: FM200/Novec1230
  • Gas weight: 1kg (T.MDC.FM.FE.1.3), 4kg (T.MDC.FM.FE.4.6), 8kg (T.MDC.FM.FE.8.6)
  • Suggested protection range: 1.59m3 (T.MDC.FM.FE.1.3), 6.3m3 (T.MDC.FM.FE.4.6), 12.6m3 (T.MDC.FM.FE.8.6)
  • Working mode: Automatic
  • Communication ports: 3 DO: Power failure, Fire alarm, and Gas spray
  • Dimensions:
    • T.MDC.FM.FE.1.3: 435mm x 3U x 650mm (w x h x d)
    • T.MDC.FM.FE.4.6: 435mm x 6U x 650mm (w x h x d)
    • T.MDC.FM.FE.8.6: 435mm x 6U x 650mm (w x h x d)


*Specifications are subject to change without notice based on technical recommendations and related product enhancements